Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/19/2013 | FIRE - ALARM FINAL | Approved | ||
| 06/17/2013 | FIRE - ALARM FINAL | Denied | FD lock system needed on gate to riser FDC or move FDC to outside the block wall Install a sign over the FDC showing placement; sign to be red 6" letters on a white background. Correct sprinkler coverage in bathroom sprinkler head blocked by bathroom fan also found cover plate painted need to replace cover plate that is factory paint. Need to have sprinkler and fire alarm contractors call in for their finals before calling in your finals. |