Permit: T13CM00859

Parcel: 122182050


Addresses:

1202 N DODGE BL

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
06/19/2013 FIRE SPKLR - FINAL Approved
06/17/2013 FIRE SPKLR - FINAL Denied FD lock system needed on gate to riser FDC or move FDC to outside the block wall
Install a sign over the FDC showing placement; sign to be red 6" letters on a white background.
Correct sprinkler coverage in bathroom sprinkler head blocked by bathroom fan also found cover plate painted need to replace cover plate that is factory paint.
Need to have sprinkler and fire alarm contractors call in for their finals before calling in your finals.