Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T13CM00825

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/09/2013 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
04/08/2013 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/08/2013 MECHANICAL - INTERMEDIATE Denied STOVE EXHAUST NOT SUPPORTED- USE DUCT STRAP OR OTHER SOLID SUPPORT. B VENT STILL HORIZONTAL
04/05/2013 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/03/2013 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*G2427.6.8.2. TYPE B VENT SHALL EXTEND VERTICALLY W/ ONE OFFSET NOT TO EXCEED 60: CORRECT SLOPE ON FURNACE VENT ALSO. SUPPORT METAL EXHAUST DUCT W/ METAL OR WOOD SPREAD FLEX DUCT SUPPORTS. 1 1/2" MIN. ADD SUPPORTS TO LINE SET AND CONDENSATE DRAINS. FIRE STOP B VENT.