Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/09/2013 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/08/2013 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/08/2013 | MECHANICAL - INTERMEDIATE | Denied | STOVE EXHAUST NOT SUPPORTED- USE DUCT STRAP OR OTHER SOLID SUPPORT. B VENT STILL HORIZONTAL | |
| 04/05/2013 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/03/2013 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*G2427.6.8.2. TYPE B VENT SHALL EXTEND VERTICALLY W/ ONE OFFSET NOT TO EXCEED 60: CORRECT SLOPE ON FURNACE VENT ALSO. SUPPORT METAL EXHAUST DUCT W/ METAL OR WOOD SPREAD FLEX DUCT SUPPORTS. 1 1/2" MIN. ADD SUPPORTS TO LINE SET AND CONDENSATE DRAINS. FIRE STOP B VENT. |