Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2013 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 05/08/2013 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/08/2013 | BUILDING - FINAL | Denied | 1. MOVE OUTLET BEHIND STOVE TO EITHER SIDE 2. INSTALL ANTI-TIP DEVICE ON STOVE 3. INSTALL ARC FAULT BREAKER FOR BEDROOM OUTLETS |
|
| 05/02/2013 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* |