Permit: T13CM00796

Parcel: 12909146C

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
05/28/2013 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
05/24/2013 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
05/24/2013 MECHANICAL - ABOVE CEILING Not ready for Inspection FLEX DUCT NOT PROPERLY SUPPORTED
1. MINIMUM WIDTH OF SUPPORT FOR FLEX DUCT IS 1/2"
2.L MAX SPACING IS 5' OR 1/2" PER FOOTSAG
3. PROVIDE FULL RADIUS BENDS
4. DO NOT SUPPORT FROM OTHER TRADES
5. SEE DETAIL MP-1