Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T13CM00796
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/28/2013 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
05/24/2013 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
05/24/2013 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | FLEX DUCT NOT PROPERLY SUPPORTED 1. MINIMUM WIDTH OF SUPPORT FOR FLEX DUCT IS 1/2" 2.L MAX SPACING IS 5' OR 1/2" PER FOOTSAG 3. PROVIDE FULL RADIUS BENDS 4. DO NOT SUPPORT FROM OTHER TRADES 5. SEE DETAIL MP-1 |