Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - ALARM FINAL
Permit Number - T13CM00743
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/27/2014 | FIRE - ALARM FINAL | Denied | Tamper failed test A/C units failed to shut down Horn/Strobe outside of crying room needs to be moved door to room when blocked open blocks the strobe. THE FOLLOWING DID PASS:: Battery test All pull stations Smoke and heat by FACP Water FLow Ground faults Horn/strobes |