Permit: T13CM00743

Parcel: 13601008J

Inspection Status: Denied

Inspection History: FIRE - ALARM FINAL

Permit Number - T13CM00743

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
01/27/2014 FIRE - ALARM FINAL Denied Tamper failed test
A/C units failed to shut down
Horn/Strobe outside of crying room needs to be moved door to room when blocked open blocks the strobe.
THE FOLLOWING DID PASS::
Battery test
All pull stations
Smoke and heat by FACP
Water FLow
Ground faults
Horn/strobes