Permit: T13CM00670

Parcel: 110071650


Addresses:

2538 N WALNUT AV

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
07/17/2013 BUILDING - FINAL Approved
06/19/2013 BUILDING - FINAL Not ready for Inspection
06/18/2013 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/18/2013 BUILDING - FINAL Denied 1. EXPOSE PORCH FOOTERS VERIFY DEPTH PER KEYNOTE
2. PORCH POSTS NOT PER PLAN 10' SPAN
3. INSTALL LAGS 24" OC PER KEYNOTE 5 @ LEDGER
4. PROVIDE PLAN FOR ALL NEW WIRING, PLUMBING, AND MECH ADDED NOT ON PLAN. TO INCLUDE FIXTURES ETC...
5. MISSING OUTLET GFCI @ COUNTER OVER 12"
6. RELOCATE SMOKE ALARMS WITHIN 36" OF FORCED AIR REGISTER
7. SECURE GAS LINE TO CODE
8. FIRE RATE EXISTING PORCH SITE PLAN KEYNOTE 2 ON PROPERTY LINE
9. GAS LINE INSTALLED TO PLAN
10. POST HOUSE NUMBERS
11. PAINT ROOF VENTS