Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T13CM00628

Parcel: 126151070


Addresses:

4321 E WHITTIER PL

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
04/26/2013 BUILDING - FINAL Approved IVRS - Inspection :*
04/17/2013 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/17/2013 BUILDING - FINAL Denied 1) MAINTAIN WORKING SPACE AT EQUIPMENT 110.26
2) PLEASE OPEN INVERTER FOR INSPECTION
3) USE LISTED/APPROVED LUGS FOR GROUNDING 690.40,41
4) SUPPORT PV CABLES AND DC DISCONNECTS UP UNDER MODULES
5) MAINTAIN FIRE ACCESS PATHS PER FIRE CODES