Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T13CM00626
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/22/2013 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
05/21/2013 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
05/21/2013 | BUILDING - FINAL | Denied | 1. PAPER WORK MISSING 2. GROUNDING ELECTRODE TO INVERTERS WRONG SIZE 3. PLASTIC WIRE TIES NOT EXCEPTABLE TO CODE 245 4. BREAKER FOR PV TOO BIG FOR 200A MAIN & LABLE DO NOT RELOCATE MISSING 5. PV COMBINER GROUNDS AND NEUTRALS TO BE SEPARATED 6. ROOF OK |