Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T13CM00607
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/09/2013 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | ||
04/09/2013 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | ||
04/09/2013 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | ||
04/09/2013 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
04/08/2013 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | THIS PROJECT IS UNDER 2012 IPC- NOT INSTALLED PER PLAN. PLAN SHOWS A FULL SIZE FLOOR CLEAN OUT DOWN STREAM OF THE TRAP. IPC DOES NOT RECOGNIZE HORIZONTAL VENTING BELOW THE FLOOD RIM. IF INSTALLING PER WPC- MET VENTED SECTIONS BETWEEN URINAL AND CLOSET TO BE 3" " WET VENTED SECTIONS TO BE ONE PIPE SIZE LARGER THAN MINIMUM WASTE SIZE FOR UPPER FIXTURE (2" URINAL" |