Permit: T13CM00607

Parcel: 10309064B

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T13CM00607

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
04/09/2013 PLUMBING - ROUGH, SOIL Not ready for Inspection
04/09/2013 PLUMBING - ROUGH, SOIL Not ready for Inspection
04/09/2013 PLUMBING - ROUGH, SOIL Not ready for Inspection
04/09/2013 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
04/08/2013 PLUMBING - ROUGH, SOIL Not ready for Inspection THIS PROJECT IS UNDER 2012 IPC- NOT INSTALLED PER PLAN. PLAN SHOWS A FULL SIZE FLOOR CLEAN OUT DOWN STREAM OF THE TRAP. IPC DOES NOT RECOGNIZE HORIZONTAL VENTING BELOW THE FLOOD RIM.
IF INSTALLING PER WPC- MET VENTED SECTIONS BETWEEN URINAL AND CLOSET TO BE 3" " WET VENTED SECTIONS TO BE ONE PIPE SIZE LARGER THAN MINIMUM WASTE SIZE FOR UPPER FIXTURE (2" URINAL"