Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T13CM00547

Parcel: 11504520A


Addresses:

1011 N TYNDALL AV


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T13CM00547

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/31/2014 MECHANICAL - FINAL Approved IVRS - Inspection :*
07/17/2014 MECHANICAL - FINAL Partial Approval SMOKE CONTROL AND AIR-BALANCE REPORTS ACCEPTED. ALL SYSTEMS ARE WITHIN ALLOWABLE TOLERANCES.
07/03/2014 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
07/03/2014 MECHANICAL - FINAL Partial Approval PROVIDE OVERFLOW SENSORS AT FAN COILS & EXTEND VENT ON TRAP. PROVIDE HOSE CLAMP ON PUMP FITTINGS. PROVIDE PROPER FUSING FOR FAN CAOLS & CONDENSORS. ROOF TOP & PENTHOUSE ROOF TOP MECHANICAL EQUITMENT IS OK