Permit: T13CM00547

Parcel: 11504520A


Addresses:

1011 N TYNDALL AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/31/2014 MECHANICAL - FINAL Approved IVRS - Inspection :*
07/17/2014 MECHANICAL - FINAL Partial Approval SMOKE CONTROL AND AIR-BALANCE REPORTS ACCEPTED. ALL SYSTEMS ARE WITHIN ALLOWABLE TOLERANCES.
07/03/2014 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
07/03/2014 MECHANICAL - FINAL Partial Approval PROVIDE OVERFLOW SENSORS AT FAN COILS & EXTEND VENT ON TRAP. PROVIDE HOSE CLAMP ON PUMP FITTINGS. PROVIDE PROPER FUSING FOR FAN CAOLS & CONDENSORS. ROOF TOP & PENTHOUSE ROOF TOP MECHANICAL EQUITMENT IS OK