Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/31/2014 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :* |
| 07/17/2014 |
MECHANICAL - FINAL |
|
Partial Approval |
SMOKE CONTROL AND AIR-BALANCE REPORTS ACCEPTED. ALL SYSTEMS ARE WITHIN ALLOWABLE TOLERANCES. |
| 07/03/2014 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 07/03/2014 |
MECHANICAL - FINAL |
|
Partial Approval |
PROVIDE OVERFLOW SENSORS AT FAN COILS & EXTEND VENT ON TRAP. PROVIDE HOSE CLAMP ON PUMP FITTINGS. PROVIDE PROPER FUSING FOR FAN CAOLS & CONDENSORS. ROOF TOP & PENTHOUSE ROOF TOP MECHANICAL EQUITMENT IS OK |