Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/13/2013 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* |
| 08/12/2013 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
1. Refer to handout, Page 13, section 412.6: minimum height of finished dam or threshold is two inches. (No dam installed) 412.8 same p[age- secure the liner to the wall per handout. 412.8(2) page 14 of handout. If you do not meet the minimum installation standard I cannot approve you. Continued not readys will result in a reinspection fee. |
| 08/09/2013 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
1. I removed the plug- the shower did not drain. Ben- I left the installation standard for shower receptors. Share it with everyone. |
| 08/08/2013 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
Unable to remove shower drain plug. Re-read shower liner requirements and complete the liner. Closet flanges OK. |
| 06/21/2013 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
1. Please review section 424.7 2012 IPC. Temperature control for two handle tub valve. Need to see shower pan test. Need to see closet flange. |