Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/20/2013 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 01/30/2013 | ELECTRIC - RECONNECT | Denied | 1. This is an underground system, remove all grounded outlets and replace with undergound outlets except gfci 2. t and p on water heater not piped 3. provide bushing where wiring enters sub panel ground extendion at subpanel not zied properly 4.All bedrooms are to have smoke detectors alarms do not install closer than 3' from suppply air outlet 5. all romex wiring in shop is to be spported and trapped in a workman like manner and as required by code all romex below 7' is to be in conduit or within covered wall to protect from damage |