Permit: T13CM00509

Parcel: 12511191E


Addresses:

811 N ALVERNON WY

Inspection Status: Cancelled

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/18/2013 ELECTRIC - FINAL Cancelled IVRS - AP canceled
11/22/2013 ELECTRIC - FINAL Not ready for Inspection #04 600 amp service SES SE House panel OK for power. OK to set meter for House Panel.
11/21/2013 ELECTRIC - FINAL Approved 04 600 AMP SERVICE SES SE HOUSE PANEL OK FOR POWER
APPROVED PLAN TO BE ON SITE . ALL REDLINES TO BE AVAILABLE AT THE TIME OF INSPECTION
11/15/2013 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
10/28/2013 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/25/2013 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/16/2013 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/16/2013 ELECTRIC - FINAL Denied - THIS IS A RE-INSPECTION, NO COMPLIANCE WITH LAST INSP NOTES. EXCEPT 42K RATED CKT BREAKERS AT SERVICE EQUIP
- PLASTIC BUSHING REQUIRED & APPROVED CABLE CONNECTORS
- INSPECTION STOPPED AT THIS POINT. CONTRACTOR TO ADDRESS SERVICE & PANELS IN UNITS
10/09/2013 ELECTRIC - FINAL Denied **NOTE: THIS INSPECTION WAS FOR METER CLEARANCE**
- BREAKER PANELS LOCATED IN CLOTHES CLOSETS - VIOLATION PER 240-24.D NEC
- SERVICE MAINS TO BE RATED 42K AIC PER ONE LINE
- PLANS CALL FOR COPPER FEEDERS TO UNITS - 1 1/2" CONDUIT
08/21/2013 ELECTRIC - FINAL Not ready for Inspection