Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T13CM00435
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/02/2013 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
02/27/2013 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. THE 2011 NATIONAL ELECTRICAL CODE SECTION 110.2 &.3 STATES ELECTRICAL EQUIPMENT TO BE PERMITTED BY THE JURISDICTION IF APPROVED. APPROVAL BY MEANS OF BEING LISTED AND IDENTIFIED BY AN OSHA APPROVED TESTING LAB WHICH ELEVATES EQUIPMENT FOR SAFETY. SEVERAL OF THE LIGHT FIXTURES SHOW COMPONENT LISTING WHICH IS LISTING OF INDIVIDUAL PARTS. THE FIXTURE IS REQUIRED TO BE LISTED AND APPROVED AS A WHOLE ASSEMBLY. THE FOLLOWING ARE A PARTIAL LIST OF FIXTURES NOT HAVING AN ASSEMBLY LISTING: 12514BF-OE1097BNN RECESSED ES8289N SUSPENDED LUMINARE CO1199BBF-RECESSED PERFORMS PRO CO 1155NBC-RECESSED LUMINARY MOD #II CO504DNBL CYLINDER 21" TRACK MOUNT OF4038BBN OCEAN 3 FIXTURE 18W T8LO OF 8042 NBN LINEAL PENDENT 39W. THIS IS A PARTIAL LIST PRIOR TO INSTALLATION PLEASE PROVIDE A LISTING FOR EACH FIXTURE TO BE USED WHICH IS APPROVED BY AN OSHA APPROVED TESTING FACILITY RAY MAJUTA |