Permit: T13CM00435

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T13CM00435

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/02/2013 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
02/27/2013 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. THE 2011 NATIONAL ELECTRICAL CODE SECTION 110.2 &.3 STATES ELECTRICAL EQUIPMENT TO BE PERMITTED BY THE JURISDICTION IF APPROVED. APPROVAL BY MEANS OF BEING LISTED AND IDENTIFIED BY AN OSHA APPROVED TESTING LAB WHICH ELEVATES EQUIPMENT FOR SAFETY.
SEVERAL OF THE LIGHT FIXTURES SHOW COMPONENT LISTING WHICH IS LISTING OF INDIVIDUAL PARTS. THE FIXTURE IS REQUIRED TO BE LISTED AND APPROVED AS A WHOLE ASSEMBLY. THE FOLLOWING ARE A PARTIAL LIST OF FIXTURES NOT HAVING AN ASSEMBLY LISTING:
12514BF-OE1097BNN RECESSED
ES8289N SUSPENDED LUMINARE
CO1199BBF-RECESSED PERFORMS PRO
CO 1155NBC-RECESSED LUMINARY MOD #II
CO504DNBL CYLINDER 21" TRACK MOUNT
OF4038BBN OCEAN 3 FIXTURE 18W T8LO
OF 8042 NBN LINEAL PENDENT 39W.
THIS IS A PARTIAL LIST PRIOR TO INSTALLATION PLEASE PROVIDE A LISTING FOR EACH FIXTURE TO BE USED WHICH IS APPROVED BY AN OSHA APPROVED TESTING FACILITY