Permit: T13CM00430

Parcel: 133170600


Addresses:

410 N WILMOT RD


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T13CM00430

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/25/2013 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
02/21/2013 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :* FAN NOT SHUTTING OFF.
02/14/2013 MECHANICAL - INTERMEDIATE Denied THE ROOF DRAINS ON THIS BLDG TERMINATE ONTO THE PARKING LOT AND SIDEALK. DO NOT TERMINATE CONDENSATE INTO A ROOF DRAIN. RUN IT INSIDE THE BLDG TO AN APPROVED LOCATION

PROVIDE A TEST ON DUCT SMOKE DETECTOR BLOCK AND CLAMP PVC ON ROOF MAX 4 INTERVALS
01/31/2013 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
THE CONDENSATE DRAIN LINE CANNOT BE REDUCED FROM THE OUTLET SIZE ON THE UNIT. PROVIDE A 1" DRAIN TO AN APPROVED LOCATION. DRAIN CANNOT TERMINATE ONTO THE PARKING LOT. THE 1/2" I.D. X 36" GAS FLEX CONNECTORE NOT ADEQUATE FOR 150,000 BTU. THIS UNIT REQUIRES A DUCT SMOKE DETECTOR WITH AN AUDIBLE AND VISIBLE ALARM. NEED TO TEST SMOKE DETECTOR.