Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T13CM00430
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/25/2013 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
02/21/2013 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* FAN NOT SHUTTING OFF. | |
02/14/2013 | MECHANICAL - INTERMEDIATE | Denied | THE ROOF DRAINS ON THIS BLDG TERMINATE ONTO THE PARKING LOT AND SIDEALK. DO NOT TERMINATE CONDENSATE INTO A ROOF DRAIN. RUN IT INSIDE THE BLDG TO AN APPROVED LOCATION PROVIDE A TEST ON DUCT SMOKE DETECTOR BLOCK AND CLAMP PVC ON ROOF MAX 4 INTERVALS |
|
01/31/2013 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* THE CONDENSATE DRAIN LINE CANNOT BE REDUCED FROM THE OUTLET SIZE ON THE UNIT. PROVIDE A 1" DRAIN TO AN APPROVED LOCATION. DRAIN CANNOT TERMINATE ONTO THE PARKING LOT. THE 1/2" I.D. X 36" GAS FLEX CONNECTORE NOT ADEQUATE FOR 150,000 BTU. THIS UNIT REQUIRES A DUCT SMOKE DETECTOR WITH AN AUDIBLE AND VISIBLE ALARM. NEED TO TEST SMOKE DETECTOR. |