Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/24/2013 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 05/20/2013 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/26/2013 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 04/26/2013 | ELECTRIC - SERVICE UPGRADE | Denied | 1) BOND BUSHING IN BOTTOM OF METER SOCKET LOOSE 2) INSTALL GROUNDING ELECTRODE TERMINAL TO MARKED POSITION AS PER INSTRUCTIONS 110.3(b) 3) VERIFY GROUND RODS LOCATION 4) GENERAL LABELING NOT PERMITTED 408.4 5) NEED BONDING DEVICE SERVICE NIPPLE 6) CANNOT FORK STRANDED CONDUCTORS OK ROOF 7) SEPERATE GROUNDS ONLY 2 PER TERMINAL ALLOWED |