Permit: T13CM00261

Parcel: 11904609B


Addresses:

444 W AJO WY

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
09/09/2015 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
09/01/2015 PLUMBING - ROUGH, SOIL Denied 1. SHALL PROVIDE A VENT FOR THE HYDRO MECHANICAL GREASE INTERCEPTOR
2. SHALL PROVIDE APPROVED MATERIAL FOR SANITARY WASTE THAT IS EXPOSED
3. ABS SCH 40 MATERIAL IS NOT APPROVED FOR OUTDOOR EXPOSED LOCATION
4. TERMINATE PREP SINK INDIRECT WASTE LINE TO EXISTING FLOOR SINK
5. RETEST DWV SYSTEM
11/10/2014 PLUMBING - ROUGH, SOIL Partial Approval EXCEPT GREASE INTERCEPTOR FICTURE P5 TO SODA DISPENSER PROVIDE RESLINE ON BUILD FOR PLAN
11/06/2014 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
11/03/2014 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*