Permit: T13CM00153

Parcel: 141305550

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T13CM00153

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/13/2013 BUILDING - FINAL Approved IVRS - Inspection :*
03/07/2013 BUILDING - FINAL Partial Approval IVRS - Inspection :#2 BREAKER STILL AN ISSUE
1. MAIN BREAKER TO BE 150 OR PLANS TO BE REVISED
02/13/2013 BUILDING - FINAL Denied 1. SCREW ON PANEL DEADFRONT TO BE REPLACE
2. BREKAER FOR PV TO BIG FOTR BUSS
3. LB ONB CAOMBINER CONNECTOR LOOSE
4. INVERTOR 1 LB CONNECTOR LOOSE
5. 3/4 IN GARAGE GOING UP TO ROOF PENTIRATION TO BE SEALED