Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - FINAL
Permit Number - T13CM00120
Inspection Description - PLUMBING - FINAL
Inspection Status - Not ready for Inspection
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2013 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 10/29/2013 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/29/2013 | PLUMBING - FINAL | Denied | SAME APPLIES TO ALL BUILDINGS. NEC 110.26A1. STORAGE TANK BLOCKING ELECTRICAL PANEL ACESS. CAP OR SECURE DRAIN DOWN VALVES. WIPE OFF EXCESS FLUX PRIOR TO INSULATING. CORRECT PIPE SIZING AT TEES. SUPPORT PIP8ING NEAR CONNECTIONS AND W/ CLEARANCE ABOVE ROOF. USE APPROVED SUPPORTS. ISOLATE CO FROM METAL. EXP TANK NOT SIZED PROPERLY. PIPE INSULATION NOT TO PLAN. MAY NOT PIGTAIL THRU WALL. |