Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/28/2014 | FIRE SPKLR - OH PIPING & HYDRO | Approved | 200 psi for 2 hours - APPROVED - Changed sprinkler head temp rating from 155 deg to 200 deg due to building has no cooler or A/C units. |