Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/11/2014 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
| 12/12/2013 | FIRE SPKLR - OH PIPING & HYDRO | Denied | 1. Flow pressure dropped to 10 PSI. Need to solve this issue. | |
| 12/11/2013 | FIRE SPKLR - OH PIPING & HYDRO | Denied | 1. PSI per the approved plans does not match the reading on the pressure gauge. 2. Plans state roughly 42 psi needed. Only 20 psi reading on gauge. |