Permit: T13BU01297

Parcel: 11106017A

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
03/21/2014 FIRE SPKLR - FINAL Approved
03/17/2014 FIRE SPKLR - FINAL Denied drain test 75-60-73
APT. #2103 AND 2101 Need to replace painted sprinkler heads in mech. rooms.
Need to add sprinkler coverage in the A/C heater room Per 2010 NFPA 13R section 6.6.4 & A6.6.4 second floor center unit.