Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T13BU01248
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/04/2014 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 01/29/2014 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 01/29/2014 | MECHANICAL - FINAL | Partial Approval | TYPE I EXHAUST FANS CANNOT BE CORD & PLUGGED. MUST BE HARD WIRED. EVERYTHING ELSE IS OK. OK TO FINAL FIRE SUPPRESSION SYSTEM. | |
| 01/27/2014 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/27/2014 | MECHANICAL - FINAL | Denied | (CORD) PIGTAIL NOT LONG ENOUGH, MAKE WIRE SPLICE INSIDE BOX ON MOTOR | |
| 12/03/2013 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 12/03/2013 | MECHANICAL - FINAL | Denied | THE FAN ON THE ROOF & RELATED DUCT WORK ARE NOT TYPE I. OPEN THE CLEANOUT DOOR ON ROOF TO INSPECT DUCT. | |
| 11/25/2013 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/25/2013 | MECHANICAL - FINAL | Denied | PROVIDE ACCESS TO ROOF. OVEN MUST BE UNDER A TYPE 1 HOOD OR REMOVE. INTERLOCK MAKEUP AIR WITH EXHAUST FAN. |