Inspection History: FIRE SPKLR - FINAL

Permit Number - T13BU01238

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/29/2014 FIRE SPKLR - FINAL Approved
04/28/2014 FIRE SPKLR - FINAL Cancelled Water accident
04/23/2014 FIRE SPKLR - FINAL Denied 2 inch drain test 80-70-85
1. Add a sign adove the FDC over the height of the wall so that FDC can be located
2. Light blocking sprinkler head in break room move light or lower sprinkler head.
3. Classroom #7 sprinkler heads covered in storage rooms
4. Fire bell failed
5. Need lock out on break for fire bell