Inspection Status: Denied
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T13BU01173
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/27/2013 | FIRE - KITCHEN EXH HOOD FINAL | Denied | Nozzles are the right ones distance is correct placement of them are correct problem is the following: 1. Gas failed to shut down when pull station was pulled need to repair or replace gas valve 2. Need Class K fire extinguisher 3. Mount conduit piping to wall above the main extinguisher tank so anything in storage room cannot pull conduit away from wall and set system off. 4. Tighten the nozzles in the duct work so that they don't move as ez. |