Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Permit Number - T13BU01173

Inspection Description - FIRE - KITCHEN EXH HOOD FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
12/27/2013 FIRE - KITCHEN EXH HOOD FINAL Denied Nozzles are the right ones distance is correct placement of them are correct problem is the following:
1. Gas failed to shut down when pull station was pulled need to repair or replace gas valve
2. Need Class K fire extinguisher
3. Mount conduit piping to wall above the main extinguisher tank so anything in storage room cannot pull conduit away from wall and set system off.
4. Tighten the nozzles in the duct work so that they don't move as ez.