Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T13BU01099
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/20/2014 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
05/09/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Partial for 4th floor south side OH/Piping. | |
04/29/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Partial to sheetrock in units 411-415. | |
04/22/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Partial for OH/Piping & Hydro south side 3rd floor. | |
03/28/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 2nd floor complete | |
03/07/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Partial for units 406-410 on 4th floor. | |
02/28/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Partial for units 306-310 on 3rd floor. | |
02/25/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Partial for 4th floor North Side 5 units. | |
02/24/2014 | FIRE SPKLR - OH PIPING & HYDRO | Denied | 4th floor building 1. Correct sprinkler spacing in hallways some 19' to 22' apart 18' x 18' heads are being used. No more than 9' off walls 2. Add spinkler head above riser 1st floor 3. Add sprinkler heads in all handi-cap bathrooms |
|
02/21/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1st floor ohpt complete. 3rd floor north ohpt complete. |
|
02/20/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Partial for 2nd floor North side OH/Piping and Hydro. | |
02/07/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Visual for 2nd floor piping on North portion of bldg. | |
01/07/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1 ammedies1st floor ohpt complete |