Permit: T13BU01066

Parcel: 11615077C

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
09/27/2013 FIRE SPKLR - FINAL Approved
09/24/2013 FIRE SPKLR - FINAL Denied Obstruction - obstruction rule for trusses, 22" inches max from deck 1" to 6" inches from bottom of trusses. I found uprights heads more than 6" from trusses will need to go through all of the building and check all upright coverage.
09/19/2013 FIRE SPKLR - FINAL Denied 1. Pendant head in electrical room needs to be removed.
2. All insulation needs to be secured to the ceiling lid.