Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/27/2013 | FIRE SPKLR - FINAL | Approved | ||
| 09/24/2013 | FIRE SPKLR - FINAL | Denied | Obstruction - obstruction rule for trusses, 22" inches max from deck 1" to 6" inches from bottom of trusses. I found uprights heads more than 6" from trusses will need to go through all of the building and check all upright coverage. | |
| 09/19/2013 | FIRE SPKLR - FINAL | Denied | 1. Pendant head in electrical room needs to be removed. 2. All insulation needs to be secured to the ceiling lid. |