Permit: T13BU01015

Parcel: 11706175A

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T13BU01015

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/14/2013 FIRE SPKLR - FINAL Approved
10/07/2013 FIRE SPKLR - FINAL Denied 1. Some of the uprights in the dining area to close to the sprayed on foam
need to keep a 1 inch plane clear from all spinkler heads.
2. Need to add sprinkler coverage under roll up door in the dinning area x3.
3. Check all outside patio sprinkler heads need to be blue color for space heaters.