Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/14/2013 | FIRE SPKLR - FINAL | Approved | ||
| 10/07/2013 | FIRE SPKLR - FINAL | Denied | 1. Some of the uprights in the dining area to close to the sprayed on foam need to keep a 1 inch plane clear from all spinkler heads. 2. Need to add sprinkler coverage under roll up door in the dinning area x3. 3. Check all outside patio sprinkler heads need to be blue color for space heaters. |