Permit: T13BU00941

Parcel: 141186320


Addresses:

9260 S HOUGHTON RD

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
02/11/2014 FIRE - ALARM FINAL Approved
01/16/2014 FIRE - ALARM FINAL Partial Approval 1. Tested the following to finish the alarm system final:
a. Water flow - Passed
b. Sprinkler bell - Passed
Tested duct smokes:
RTU -1 - Passed
RTU-4 - Passed
RTU -8 - Passed
RTU-9 - Failed bad transformer for smoke
RTU-10 - Passed
RTU-11 - Passed
RTU- 12- Passed
RTU-13 - Passed
RTU-18 - Passed
AHU-1 - Passed
AHU-2 - Failed bad duct smoke detector
Hood final - Passed
Will need to re-test the failed sections
01/14/2014 FIRE - ALARM FINAL Partial Approval 1. Tested tampers, smoke, and pull station. All okay.
2. Still need to test Ansul system and duct detectors.