Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T13BU00941
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/11/2014 | FIRE - ALARM FINAL | Approved | ||
| 01/16/2014 | FIRE - ALARM FINAL | Partial Approval | 1. Tested the following to finish the alarm system final: a. Water flow - Passed b. Sprinkler bell - Passed Tested duct smokes: RTU -1 - Passed RTU-4 - Passed RTU -8 - Passed RTU-9 - Failed bad transformer for smoke RTU-10 - Passed RTU-11 - Passed RTU- 12- Passed RTU-13 - Passed RTU-18 - Passed AHU-1 - Passed AHU-2 - Failed bad duct smoke detector Hood final - Passed Will need to re-test the failed sections |
|
| 01/14/2014 | FIRE - ALARM FINAL | Partial Approval | 1. Tested tampers, smoke, and pull station. All okay. 2. Still need to test Ansul system and duct detectors. |