Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T13BU00911
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/31/2013 | FIRE - ALARM FINAL | Approved | ||
10/23/2013 | FIRE - ALARM FINAL | Denied | 1. Duct smoke failed to shut down A/C units 2. By front door bad pull station 3. Need lock on breaker to the FACP 4. Need a UL/FM cert. for monitoring set to the fire department. 5. Need plans to that show changes were made, according to the plans system was to be wired as a class "A" system but only the storbes are and not the pull stations, will need to change the plans or wire per approved plans. |