Permit: T13BU00897

Parcel: 10703141D

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
11/14/2013 FIRE SPKLR - FINAL Approved
10/17/2013 FIRE SPKLR - FINAL Denied 1. Add drain as stated on approved plans
2. Move heads 4" inches or more from braces
3. Need 5 year check valve inspection
4. Add a sign on riser door "RISER ROOM"