Permit: T13BU00779

Parcel: 13317066B


Addresses:

1031 N PARK AV


Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Permit Number - T13BU00779

Inspection Description - FIRE SPKLR - OH PIPING & HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
07/15/2014 FIRE SPKLR - OH PIPING & HYDRO Approved
05/09/2014 FIRE SPKLR - OH PIPING & HYDRO Cancelled IVRS - RI canceled
05/09/2014 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1. Partial for 200 psi test on standpipes.
2. Okay to remove sidewall sprinkler head in elevator repair room.
04/17/2014 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1. Partial for OH/Piping & Hydro for steel piping in underground Parking 1 & 2.
04/03/2014 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1. Partial for 13th floor OH/Piping & Hydro.
03/25/2014 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1. 1st and 12th floor 200 pound pressure test complete
03/18/2014 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1. Partial for 10th & 11th floor OH/Piping & Hydro.
03/05/2014 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1. Partial for 9th floor OH/Piping & Hydro.
02/11/2014 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1. Partial for 8th floor OH/Piping & Hydro.
02/03/2014 FIRE SPKLR - OH PIPING & HYDRO Partial Approval Partial for 7th floor OH/Piping & Hydro - 200 PSI for 2 hours
Make sure to check all fire caulking where piping goes through wall into hallway
01/23/2014 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1. Partial for 6th floor OH/Piping & Hydro.
01/16/2014 FIRE SPKLR - OH PIPING & HYDRO Partial Approval Partial for 5th floor OH/Piping & Hydro - 200 PSI for 2 hours
01/09/2014 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1. Partial for 4th floor OH/Piping & Hydro.
12/18/2013 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1. Partial for 3rd floor OH/Piping & Hydro.
12/04/2013 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1. Partial for 2nd floor OH/Piping & Hydro.