Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T13BU00779
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/15/2014 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
05/09/2014 | FIRE SPKLR - OH PIPING & HYDRO | Cancelled | IVRS - RI canceled | |
05/09/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Partial for 200 psi test on standpipes. 2. Okay to remove sidewall sprinkler head in elevator repair room. |
|
04/17/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Partial for OH/Piping & Hydro for steel piping in underground Parking 1 & 2. | |
04/03/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Partial for 13th floor OH/Piping & Hydro. | |
03/25/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. 1st and 12th floor 200 pound pressure test complete | |
03/18/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Partial for 10th & 11th floor OH/Piping & Hydro. | |
03/05/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Partial for 9th floor OH/Piping & Hydro. | |
02/11/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Partial for 8th floor OH/Piping & Hydro. | |
02/03/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | Partial for 7th floor OH/Piping & Hydro - 200 PSI for 2 hours Make sure to check all fire caulking where piping goes through wall into hallway |
|
01/23/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Partial for 6th floor OH/Piping & Hydro. | |
01/16/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | Partial for 5th floor OH/Piping & Hydro - 200 PSI for 2 hours | |
01/09/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Partial for 4th floor OH/Piping & Hydro. | |
12/18/2013 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Partial for 3rd floor OH/Piping & Hydro. | |
12/04/2013 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Partial for 2nd floor OH/Piping & Hydro. |