Permit: T13BU00767

Parcel: 11504520B


Addresses:

1011 N TYNDALL AV


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T13BU00767

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/31/2014 FIRE SPKLR - FINAL Approved
07/02/2014 FIRE SPKLR - FINAL Partial Approval 1. fire pump test passed.
2. need paperwork on firepump test.
3. jocky pump is running to often there appears to be a leak.