Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T13BU00767
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/25/2014 | FIRE SPKLR - OH PIPING & HYDRO | Approved | 200 pound test complete all floors | |
03/14/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. 12th floor complete. | |
02/28/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 11th floor complete | |
02/21/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 10th floor ohpt complete | |
02/14/2014 | FIRE SPKLR - OH PIPING & HYDRO | Basin in Poor Condition | 9th floor ohpt complete | |
02/07/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 8th floor ohpt complete | |
02/04/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 7th floor ohpt complete | |
01/22/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 6th floor - 200 psi for 2 hours 1. 6TH FL. Rm 607 add sprinkler coverage in bike rack area 2. Between 609 & 610 hallway closet add sprinkler coverage 3. Correct sprinkler coverage in room 613 pendent to far off wall 9' 6" head is designed for 16X 16. Keep sidewall heads 12" away from A/C registers |
|
01/09/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. 5th floor ohpt complete | |
01/08/2014 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. 2nd floor is completely done. | |
12/27/2013 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Fourth floor pressure test and ohp inspection complete. | |
12/19/2013 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. third floor ohpt complete. | |
11/22/2013 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. 1st floor complete. 2. 2nd floor parking garage complete. 3. 2nd floor still needs hallways and 201 done every thing else passed. |