Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T13BU00676
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/13/2014 | FIRE - ALARM FINAL | Approved | ||
01/28/2014 | FIRE - ALARM FINAL | Denied | Non-listed smoke detector installed in trash shoot rooms & not connected to the fire alarm system | |
12/18/2013 | FIRE - ALARM FINAL | Denied | 1. Wire fire bell 2. Wire and test elevator operations 3. Install outside horn/strobe on roof top 4. All fire/smoke dampers shall close when fire alarm actives 5. Need to test smoke for elevators |
|
12/05/2013 | FIRE - ALARM FINAL | Partial Approval | While completing fire pump test the following alarm signals to FACP done: 1. Tested reversal Phase - PASSED 2. Pump run - PASSED 3. Power frailer to pump - PASSED 4. Tampers to FR1 - FR2 - FR3 - PASSED (FR = Fire Riser) 5. Flow switch for FR1 - 47 secs 6. Flow switch for FR2 - 52 secs 7. Flow switch for FR3 - 57 secs |