Permit: T13BU00676

Parcel: 11712087C


Addresses:

1 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T13BU00676

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/13/2014 FIRE - ALARM FINAL Approved
01/28/2014 FIRE - ALARM FINAL Denied Non-listed smoke detector installed in trash shoot rooms & not connected to the fire alarm system
12/18/2013 FIRE - ALARM FINAL Denied 1. Wire fire bell
2. Wire and test elevator operations
3. Install outside horn/strobe on roof top
4. All fire/smoke dampers shall close when fire alarm actives
5. Need to test smoke for elevators
12/05/2013 FIRE - ALARM FINAL Partial Approval While completing fire pump test the following alarm signals to FACP done:
1. Tested reversal Phase - PASSED
2. Pump run - PASSED
3. Power frailer to pump - PASSED
4. Tampers to FR1 - FR2 - FR3 - PASSED (FR = Fire Riser)
5. Flow switch for FR1 - 47 secs
6. Flow switch for FR2 - 52 secs
7. Flow switch for FR3 - 57 secs