Permit: T13BU00612

Parcel: 136129510

Inspection Status: Approved

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Date Description Inspector Results Comments
06/19/2013 FIRE SPKLR - UG, PIPING, HYDRO Approved
05/30/2013 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval Okay to bury this inspection was for visual inspection only - Still need to complete a 200 PSI test for 2 hours and a flush - flushing line can not be smaller than 4 inches.