Permit: T13BU00505

Parcel: 140420270


Addresses:

2650 E ELVIRA RD

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
06/27/2013 FIRE - ALARM FINAL Approved
06/06/2013 FIRE - ALARM FINAL Denied Panel needs to be clear of all troubles signals at all times, when testing was completed for the new horn/strobes the main fire alarm panel shows a trouble signal.
All horn/strobes need to be in synchronization
Add coverage in the labs rooms where no audio/visual can be seen or heard.
All smoke duct detectors shall report as a supervisory signal to the fire alarm control panel.
In clean room 1 needs cover of a horn/strobe
Change out strobe light in machine room for a strobe/horn as per approved plans.