Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T13BU00505
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/27/2013 | FIRE - ALARM FINAL | Approved | ||
06/06/2013 | FIRE - ALARM FINAL | Denied | Panel needs to be clear of all troubles signals at all times, when testing was completed for the new horn/strobes the main fire alarm panel shows a trouble signal. All horn/strobes need to be in synchronization Add coverage in the labs rooms where no audio/visual can be seen or heard. All smoke duct detectors shall report as a supervisory signal to the fire alarm control panel. In clean room 1 needs cover of a horn/strobe Change out strobe light in machine room for a strobe/horn as per approved plans. |