Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T13BU00432
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/26/2013 | FIRE SPKLR - FINAL | Approved | ||
08/22/2013 | FIRE SPKLR - FINAL | Denied | 1. No bell need to install 2. Room #2 sprinkler head problem in the hot water heater room - check room again 3. Room #3 Upright by front t door needs to be 12" from deck. Check Kitchen and in closet. - check room again 4. Room #5 sprinkler head taped in closet - check room again 5. Room #7 Check for taped head - check room again 6. Room #9 Check sprinklers in closets - check room again 7. Still need to do flow test and get flow readings 8. Need signs on inspectors test valve and signs on riser 9. Need sign on riser room door label "RISER ROOM" |
|
07/16/2013 | FIRE SPKLR - FINAL | Denied | Need as bults before final will be given |