Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T13BU00432
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/21/2013 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
07/16/2013 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | Passed 200 PSI for 2 hours but the placement of heads are in question some heads are 17" below deck all outside sidewall heads are 15 to 17 inches below deck, small closets with water heater above not covered need heads added, couple closets block sprinkler coverage from above (spray obstruction). No more than 12 inches allowed from deck. | |
07/11/2013 | FIRE SPKLR - OH PIPING & HYDRO | Cancelled | IVRS - RI canceled |