Permit: T13BU00423

Parcel: 141386920

Inspection Status: Approved

Inspection History: POOL/SPA PRE-GUNITE

Permit Number - T13BU00423

Inspection Description - POOL/SPA PRE-GUNITE

Inspection Status - Approved

Date Description Inspector Results Comments
04/26/2013 POOL/SPA PRE-GUNITE Approved IVRS - Inspection :*
04/24/2013 POOL/SPA PRE-GUNITE Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/24/2013 POOL/SPA PRE-GUNITE Denied -HIGH HAZARD BACKFLOW ASSEMBLY NEEDED FOR AUTO POOL FILL
-HORIZONTAL REBAR EXCEEDS SPACING AT BACK WALL OF SPA
-BONDING GRID NEEDED TO ENCIRCLE POOL W/ 4 PIGTAILS ATTACHED TO REBAR
-HEATER BOND?
-PROVIDE LITERATURE FOR APPROVAL OF 2 BOND WIRES INTO SINGLE REBAR CLAMP FROM MANUFACTURE
-RECONNECT GROUNDING CONDUCTOR TO 2ND GROUND ROD FOR MAIN PANEL
-18" MINIMUM BURIAL NEEDED ON TOP OF PLASTIC GAS LINE
-REBAR REINFORCEMENT AROUND SPA LIGHT PER ENGINEERING SPECS