Inspection History Details
Inspection Status: Closed
Inspection History: FIRE SPKLR - FINAL
Permit Number - T13BU00265
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Closed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/07/2022 | FIRE SPKLR - FINAL | Closed | CONTRACTOR DID NOT CALL IN PERMIT TO COMPLETE FINAL | |
03/27/2013 | FIRE SPKLR - FINAL | Correction Required | 1. Need as builds for changes 2. Correct coverage in stairwell to roof by adding heads above landing and opening 3. Add coverage in the north elevator room 4. Add coverage in the mech. room head block by sheet metal. 5. Need to make up riser 6. Need to test new tamper and flow switch |