Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T13BU00255
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/24/2014 | FIRE SPKLR - FINAL | Approved | ||
12/18/2013 | FIRE SPKLR - FINAL | Partial Approval | Tested tapers and flow switches in the following areas: 1st floor tamper - passed Flow switch - 32.26 sec 2nd floor tamper - passed Flow switch - 40.81 sec 3rd floor tamper - passed Flow switch - 37.53 sec 4th floor tamper - passed Flow switch - 32.83 sec 5th floor tamper - passed Flow switch - 34.00 sec 6th floor tamper - passed Flow switch - 54.00 sec 7th floor tamper - passed Flow switch - 34.00 sec 1. 7th floor elevator lobby missing ceiling 2. Rm 708 bedroom ceiling 3. Rm 610 bathroom hole in wall 4. Rm 609 Painted head bedroom 5. 3rd floor by west stairwell heads blocked by led lights |
|
12/05/2013 | FIRE SPKLR - FINAL | Partial Approval | Fire Pump test completed - PASSED 2in drain test - 50-49-52 NOTE PUMP PANEL has a transfer switching for EM generator but is not going to be used, is not required be wired and owner does not want to pay for extra wiring. While completing fire pump test the following alarm signals to FACP done: 1. Tested reversal Phase - PASSED 2. Pump run - PASSED 3. Power frailer to pump - PASSED 4. Tampers to FR1 - FR2 - FR3 - PASSED (FR = Fire Riser) 5. Flow switch for FR1 - 47 secs 6. Flow switch for FR2 - 52 secs 7. Flow switch for FR3 - 57 secs |