Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T13BU00255

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/24/2014 FIRE SPKLR - FINAL Approved
12/18/2013 FIRE SPKLR - FINAL Partial Approval Tested tapers and flow switches in the following areas:
1st floor tamper - passed
Flow switch - 32.26 sec
2nd floor tamper - passed
Flow switch - 40.81 sec
3rd floor tamper - passed
Flow switch - 37.53 sec
4th floor tamper - passed
Flow switch - 32.83 sec
5th floor tamper - passed
Flow switch - 34.00 sec
6th floor tamper - passed
Flow switch - 54.00 sec
7th floor tamper - passed
Flow switch - 34.00 sec
1. 7th floor elevator lobby missing ceiling
2. Rm 708 bedroom ceiling
3. Rm 610 bathroom hole in wall
4. Rm 609 Painted head bedroom
5. 3rd floor by west stairwell heads blocked by led lights
12/05/2013 FIRE SPKLR - FINAL Partial Approval Fire Pump test completed - PASSED
2in drain test - 50-49-52
NOTE PUMP PANEL has a transfer switching for EM generator but is not going to be used, is not required be wired and owner does not want to pay for extra wiring.
While completing fire pump test the following alarm signals to FACP done:
1. Tested reversal Phase - PASSED
2. Pump run - PASSED
3. Power frailer to pump - PASSED
4. Tampers to FR1 - FR2 - FR3 - PASSED (FR = Fire Riser)
5. Flow switch for FR1 - 47 secs
6. Flow switch for FR2 - 52 secs
7. Flow switch for FR3 - 57 secs