Permit: T13BU00255

Parcel: 11712087C


Addresses:

1 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Permit Number - T13BU00255

Inspection Description - FIRE SPKLR - OH PIPING & HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
12/18/2013 FIRE SPKLR - OH PIPING & HYDRO Approved
11/18/2013 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 200 psi for 2 hours test on both stairwells 1 & 2 standpipes only - PASSED
10/17/2013 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 7th floor OH 200 psi for 2 hours and placement APPROVED
09/27/2013 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 6th floor ohpt passed.
need to check placement in stairwell on final #2
07/03/2013 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1. Partial for 200psi on 5th floor.
06/05/2013 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1. lower level 200 psi passed. stand pipes to be tested later date.
2. fourth floor 200 psi passed .
06/03/2013 FIRE SPKLR - OH PIPING & HYDRO Partial Approval Basement failed leaking pipe
200 PSI testing and overhead placement approved in the following areas:
1st floor - still need to check the trash shoot area (northwest corner)
2nd floor - Need to check ramp from 2nd floor to outside road piping not made up due roll down doors going in, also check south side by 2nd stairwell head block by pillar.
3rd floor - check south side by 2nd stairwell head block by pillar.