Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T13BU00178

Parcel: 12801005H

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T13BU00178

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/27/2013 FIRE SPKLR - FINAL Approved
02/22/2013 FIRE SPKLR - FINAL Denied Contractor called for sprinkler final under his permit T12CM08122, Kazal fire needs to pay for there permit T13BU00178.
I did a sprinkler inspection for final and found sprinkler coverage not adequate on sales floor; sprinkler heads are 8' 11" off wall to far needs to be 7' 6" off wall need to correct coverage.