Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T13BU00076
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/26/2013 | FIRE - KITCHEN EXH HOOD FINAL | Denied | All electrical shall shut down when system is activated. | |
03/26/2013 | FIRE - KITCHEN EXH HOOD FINAL | Approved | ||
03/21/2013 | FIRE - KITCHEN EXH HOOD FINAL | Denied | On site contractor stated they are not ready still need to install gas valve and run cable for operations should not take more 3 to 4 hours to install. Advise to call in for finals for Friday. | |
03/14/2013 | FIRE - KITCHEN EXH HOOD FINAL | Denied | On site no one on site to do final, looked at both hoods found a gas line going to ovens plans show and say no gas valves. I talked to the contractor found out they are not ready I advise him that the approved plans stated no gas valves when there is a gas line install. They will need to revise plans showing gas valves, contractor also stated there are more changes advise him new plans will be needed before final will be done or given. |