Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T13BU00003
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/22/2013 | FIRE - ALARM FINAL | Approved | ||
01/09/2013 | FIRE - ALARM FINAL | Denied | On 1st - 2nd & 3rd floor elevator lobbies all fire doors shall close completely and latch shut when in alarm condition for proper ventilation for the atrium. Need to replace all doors. Make sure to use only approved fire hardware for the fire doors (ie. Panic hardware, door hinges, and door closers that work with the alarm system). Shall repair or replace horn/strobes in the following areas: Rooms 265 - 175 - 3rd floor elevator lobby and hiding above ceiling in 235. |