Permit: T12PL00307

Parcel: 105102440


Addresses:

495 E WETMORE RD

Inspection Status: Denied

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
08/31/2012 PLUMBING - INTERMEDIATE Denied 1. At frease trap: Down stream of the grease trap requires an approved vent. Flow control device is not approved for this vent. 2. Flow control be installed in a visible and readily accessible location (at the fixture). 3. Sanitizing bowl for the three compartment sink is to be indirectly wasted. 4. Connections for the other two bowls to be drainage fittings. Fourth bowl may not be connected to the three compartment sink. 5. Three compartment sink (two bowls) require a connecting vent between the fixture trap and the flow control. The flow control vent may not terminate in the room. 6. Have the plumber on site for the next inspection.