Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T12PL00245
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/22/2012 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
02/15/2012 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1) NOBODY HOME 2) REQUIRE 10 POUND TEST ON SYSTEM, REFER TO HAND OUT 3) REQUIRE AGA OR CSA APPROVED VALVES 4) T & P RELIEF DRAIN TO EXTEND TO OUTSIDE AND POINT DOWN 5) REQUIRE SHUT OFF VALVE AT COLD INLET TO WATER HEATER 6) WATER HEATER TO SIT ON AN APPROVED BASE |
|
02/13/2012 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* |