Permit: T12PL00237

Parcel: 133290180


Addresses:

8630 E VICKSBURG ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/21/2012 PLUMBING - FINAL Approved IVRS - Inspection :*
02/15/2012 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) VENT CONNECTOR REQUIRES SLOPE
2) ALIGN DRAFT CONNECTOR OVER WATER HEATER VENT AND SECURE
3) AIR GAP REQUIRED ABOVE WATER HEATER PAN FOR RELIEF DRAIN
4) FURNACE VENT REQUIRES A LISTED 4 X 6 ADAPTOR, ALSO INCREASE 3" TO 4" AT FURNACE CONNECTION
5) BOTH VENTS ARE REQUIRED TO TERMINATE 3' ABOVE COOLER
6) SECURE YOUR FLASHINGS WITH COATED ROOFING FASTENERS
7) BONDING- ALSO REPLACE MISSING BOND FOR WATER LINE
02/10/2012 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) ACCESS TO ROOF REQUIRED
2) SECURE PIPING AT FURNACE
3) PROVIDE ELECTRICAL BOND
4) CORRECT VENTING FOR BOTH APPLIANCES; APPROVED FITTINGS, PROPERLY INSTALLED AND SECURED
5) PROVIDE APPROVED RELIEF VALVE PIPING AND TERMINATION
6) NEW WATER LINE REQUIRES PERMIT
7) MISSING VACUUM BREAKER